Your cart has 0 item(s), Totalling £0.00
-
Home > Other
Schneider Electric Compact NS800N 4 Pole 800A Electric Circuit Breaker Chassis
Click the image to expand
Schneider Electric Compact NS800N 4 Pole 800A Electric Circuit Breaker Chassis Schneider Electric Compact NS800N 4 Pole 800A Electric Circuit Breaker Chassis Schneider Electric Compact NS800N 4 Pole 800A Electric Circuit Breaker Chassis Schneider Electric Compact NS800N 4 Pole 800A Electric Circuit Breaker Chassis

Schneider Electric Compact NS800N 4 Pole 800A Electric Circuit Breaker Chassis

Brand: Schneider
MPN:33334 33525 33725 33735 33736 33164
Product Condition: Used
Quantity:
Excluding VAT: £760.00
Including VAT:£912.00
Schneider Electric Compact NS800N 4 Pole 800A Electric Circuit Breaker Chassis
NS800N

 
In good condition and full working order

 
Main
Device short name Compact NS800N
Circuit breaker name Compact NS800N
Poles description 4P
Neutral position Left
Network type AC
Circuit breaker rating code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Complementary
Network frequency 50/60 Hz
Control type Rotary handle
Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
[In] rated current 800 A ( 50 °C )
[Ui] rated insulation voltage 800 V conforming to IEC 60947-2 AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
[Ue] rated operational voltage 690 V conforming to IEC 60947-2 AC 50/60 Hz
Circuit breaker CT rating 800 A
Breaking capacity 25 kA conforming to NEMA AB1 HIC at 600 V AC 60 Hz
35 kA conforming to NEMA AB1 HIC at 480 V AC 60 Hz
50 kA conforming to NEMA AB1 HIC at 240 V AC 60 Hz
30 kA Icu conforming to IEC 60947-2 at 660/690 V AC 50/60 Hz
40 kA Icu conforming to IEC 60947-2 at 500/525 V AC 50/60 Hz
50 kA Icu conforming to IEC 60947-2 at 220/240 V AC 50/60 Hz
50 kA Icu conforming to IEC 60947-2 at 380/415 V AC 50/60 Hz
50 kA Icu conforming to IEC 60947-2 at 440 V AC 50/60 Hz
[Ics] rated service breaking capacity Ics 30 kA conforming to IEC 60947-2 660/690 V AC 50/60 Hz manual operation
Ics 40 kA conforming to IEC 60947-2 500/525 V AC 50/60 Hz manual operation
Ics 50 kA conforming to IEC 60947-2 220/240 V AC 50/60 Hz manual operation
Ics 50 kA conforming to IEC 60947-2 380/415 V AC 50/60 Hz manual operation
Ics 50 kA conforming to IEC 60947-2 440 V AC 50/60 Hz manual operation
Mechanical durability 10000 cycles conforming to IEC 60947-2
Electrical durability 2000 cycles conforming to IEC 60947-2 690 V In AC 50/60 Hz
4000 cycles conforming to IEC 60947-2 690 V In/2 AC 50/60 Hz
5000 cycles conforming to IEC 60947-2 440 V In AC 50/60 Hz
6000 cycles conforming to IEC 60947-2 440 V In/2 AC 50/60 Hz
Connection pitch 70 mm
[Icw] rated short-time withstand current 19.2 kA ( 1 s ) conforming to IEC 60947-2
Integral instant protection 40 kA
Height 327 mm
Width 280 mm
Depth 147 mm
Environment
Standards IEC 60947-2
NEMA AB1 HIC
Product certifications ASEFA
ASTA
LCIE
Pollution degree 3 conforming to IEC 60947
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C

Schneider Merlin Gerin Compact NS > 630A NS800 N 4P BASIC BREAKER DRAWOUT VERSION (33334)

Main

range of product
NS630b...1600
device short name
Compact NS800N
circuit breaker name
Compact NS800N
poles description
4P
neutral position
Left
network type
AC
breaking capacity code
N
suitability for isolation
Yes conforming to IEC 60947-2
utilisation category
Category B

Complementary

network frequency
50/60 Hz
control type
Toggle
mounting mode
Drawout
mounting support
Backplate
upside connection
Front
downside connection
Front
rated current
800 A ( 50 °C )
rated insulation voltage
800 V AC 50/60 Hz conforming to IEC 60947-2
rated impulse withstand voltage
8 kV conforming to IEC 60947-2
rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
circuit breaker CT rating
800 A
breaking capacity
25 kA at 600 V AC 60 Hz conforming to NEMA AB1 HIC
35 kA at 480 V AC 60 Hz conforming to NEMA AB1 HIC
50 kA at 240 V AC 60 Hz conforming to NEMA AB1 HIC
Icu 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Icu 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
rated service breaking capacity
Ics 30 kA 660/690 V AC 50/60 Hz manual operation conforming to IEC 60947-2
Ics 40 kA 500/525 V AC 50/60 Hz manual operation conforming to IEC 60947-2
Ics 50 kA 220/240 V AC 50/60 Hz manual operation conforming to IEC 60947-2
Ics 50 kA 380/415 V AC 50/60 Hz manual operation conforming to IEC 60947-2
Ics 50 kA 440 V AC 50/60 Hz manual operation conforming to IEC 60947-2
mechanical durability
10000 cycles conforming to IEC 60947-2
electrical durability
2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
connection pitch
70 mm
rated short-time withstand current
19.2 kA ( 1 s ) conforming to IEC 60947-2
integral instant protection
40 kA
height
327 mm
width
280 mm
depth
147 mm

Environment

standards
IEC 60947-2
NEMA AB1 HIC
product certifications
ASEFA
ASTA
LCIE
pollution degree
3 conforming to IEC 60947
ambient air temperature for operation
-25...70 °C
ambient air temperature for storage
-50...85 °C



 
VAT IS NOT PAYABLE BY PURCHASERS OUTSIDE THE European Union (EU) AND by purchasers in the EU (excluding UK) who are VAT registered
Delivery is with UPS


Any Questions? Please call 020 8882 1111 from UK or +44 208882 1111 from outside the UK

SL 86065 86068 IB 92236
SL 86066 86069 IB 92236

To request a price please fill out the form below...

Close